Energy Performance Modeling of an Office Building and Its Evaluation – Post-Occupancy Evaluation and Energy Efficiency of the Building |
doi |
https://doi.org/10.52842/conf.caadria.2013.209
|
source |
Open Systems: Proceedings of the 18th International Conference on Computer-Aided Architectural Design Research in Asia (CAADRIA 2013) / Singapore 15-18 May 2013, pp. 209-218 |
wos |
WOS:000351496100021 |
summary |
Energy performance modelling can provide insights into the efficiency and sustainability of commercial buildings, and also the achievement of certification standards such as USGBC LEED. However, the results from the modelling must be validated via a post-construction evaluation, which quantifies any discrepancies between the predicted energy usage and the actual energy consumed. In this study, an existing office building was examined to test how well the model predicts energy usage. The results from the model were compared with the actual usage of gas and electricity over two years (2010-2011). Our study showed a 123% higher gas usage,and a 36% lower electricity, compared with the simulation. This difference presents that occupant behaviour and building construction practices have significant impact on the energy usage of a building. For instance, the large discrepancy among gas usage is due to the office building’s thermal envelope, which identifies the spots at which heat leaks out of the building, thereby forcing the heating unit to work more. Additionally, the post occupancy evaluation study identified that indoor environmental conditions impact on energy consumption of the building. |
keywords |
Building performance evaluation, Energy modelling, Energy usage, User behaviour, Post occupancy evaluation |
series |
CAADRIA |
email |
|
full text |
file.pdf (1,047,324 bytes) |
references |
Content-type: text/plain
|
ASHRAE (2010)
Performance Measurement Protocols for Commercial Buildings
, American Society of Heating, Refrigerating and Air Conditioning Engineers
|
|
|
|
Aziz, A., Park, J., et al. (2012)
Field measurement Protocols for Evaluating Indoor Environmental Quality and User Satisfaction in Relation to Energy Efficiency
, U.S. DOE The Energy Efficient Buildings Hub, Department of Energy
|
|
|
|
CBECS (2003)
2003 Commercial Buildings Energy Consumption Survey (CBECS)
, Department of Energy, USA
|
|
|
|
Effinger, J., Effinger, M. and Kramer, H. (2012)
Overcoming Barriers to Whole Building M&V in Commercial Buildings
, 2012 ACEEE Summer Study on Energy Efficiency in Buildings, American Council for an Energy-Efficient Economy, Washington, DC
|
|
|
|
Gundala, S. (2003)
LEED Energy Performance Modeling and Evaluation of the S.T. Dana Building Renovations
, Report No. CSS03-07, Center for Sustainable Systems, University of Michigan, Ann Arbor, MI
|
|
|
|
Loftness, V., Aziz, A., Choi, J. H., Kampschroer, K., Powell, K., Atkinson, M. and Heerwagen J. (2009)
The value of post-occupancy evaluation for building occupants and facility managers
, Intelligent Buildings International, 1(4), 249–268
|
|
|
|
Raftery, P., Keane M. and Costa, A. (2009)
Calibration of a detailed simulation model to energy monitoring system data: a methodology and case study
, Proceedings of the 11th IBPSA Conference, Glasgow, UK
|
|
|
|
Yoshino, H. (2009)
Total energy use in buildings: analysis and evaluation methods
, ECBCS Project Factsheet, Annex 53, ECBCS, UK
|
|
|
|